Annual report summary

PETERSBURG: Annual Water Quality Report 2025 Summary

15 reviewed rows from the 2025 report for PWSID AK2130148, shown with the original report source and row-level context.

Reviewed annual reportSource retrieved: Data reviewed:

Report identity and source

Public water system
PETERSBURG
PWSID
AK2130148
Report year
2025
Official publisher/source
Petersburg Borough / Petersburg Water Utility Annual Water Quality Report 2025
Source retrieved
2026-07-22
Last reviewed
2026-07-22

Reviewed Report Rows

15 reviewed rows from the 2025 report

Measurements, ranges, units, limit fields, status cells, likely-source wording, and table names remain scoped to the named annual-report rows.

Inorganic and radioactive results

Nine reported rows, including action-level and below-reporting-limit results.

Inorganic and radioactive results: 2025 annual-report rows for PETERSBURG
Report rowReported measurementRange in reportSites above action levelTesting period in reportUnitLimit or standard fieldStatus printed for this rowSource pageSource table
Gross Alpha (2025)Detected Level: 0No separate range printedNot listed for this report row2025pCi/LMCL Goal: 0; MCL: 15SYSTEM in VIOLATION: NO (row sample period)22025 Annual Treated Drinking Water Quality Report - Inorganic
Radium 226 (2025)Detected Level: 0No separate range printedNot listed for this report row2025pCi/LMCL Goal: 0; MCL: 5SYSTEM in VIOLATION: NO (row sample period)22025 Annual Treated Drinking Water Quality Report - Inorganic
Radium 228 (2025)Detected Level: 0No separate range printedNot listed for this report row2025pCi/LMCL Goal: 0; MCL: 5SYSTEM in VIOLATION: NO (row sample period)22025 Annual Treated Drinking Water Quality Report - Inorganic
Barium (2019)Detected Level: 8.8No separate range printedNot listed for this report row2019PpbMCL Goal: 2,000; MCL: 2,000SYSTEM in VIOLATION: NO (row sample period)22025 Annual Treated Drinking Water Quality Report - Inorganic
Copper (2024)Detected Level: 24No separate range printedNo sites above action level2024PpbMCL Goal: 1300; MCL / AL: 1300 (AL)SYSTEM in VIOLATION: NO (row sample period)22025 Annual Treated Drinking Water Quality Report - Inorganic
FluorideDetected Level average: 0.70 avg; 0.70 avg.0.5-0.9Not listed for this report rowJanuary 1-December 31, 2025PpmMCL Goal: 4; MCL: 4SYSTEM in VIOLATION: NO (row report period)22025 Annual Treated Drinking Water Quality Report - Inorganic
Selenium (2019)Detected Level: <MRL<MRLNot listed for this report row2019PpbMCL Goal: 50; MCL: 50SYSTEM in VIOLATION: NO (row sample period)22025 Annual Treated Drinking Water Quality Report - Inorganic
Lead (2024)Detected Level: 3.5No separate range printedNo sites above action level2024PpbMCL Goal: 0; MCL / AL: 15 (AL)SYSTEM in VIOLATION: NO (row sample period)22025 Annual Treated Drinking Water Quality Report - Inorganic
Nitrate/NitriteDetected Level: 0.033No separate range printedNot listed for this report rowJanuary 1-December 31, 2025PpmMCL Goal: 10; MCL: 10SYSTEM in VIOLATION: NO (row report period)22025 Annual Treated Drinking Water Quality Report - Inorganic
Report rowGross Alpha (2025)
Reported measurementDetected Level: 0
Range in reportNo separate range printed
Sites above action levelNot listed for this report row
Testing period in report2025
UnitpCi/L
Limit or standard fieldMCL Goal: 0; MCL: 15
Status printed for this rowSYSTEM in VIOLATION: NO (row sample period)
Source page2
Source table2025 Annual Treated Drinking Water Quality Report - Inorganic
Report rowRadium 226 (2025)
Reported measurementDetected Level: 0
Range in reportNo separate range printed
Sites above action levelNot listed for this report row
Testing period in report2025
UnitpCi/L
Limit or standard fieldMCL Goal: 0; MCL: 5
Status printed for this rowSYSTEM in VIOLATION: NO (row sample period)
Source page2
Source table2025 Annual Treated Drinking Water Quality Report - Inorganic
Report rowRadium 228 (2025)
Reported measurementDetected Level: 0
Range in reportNo separate range printed
Sites above action levelNot listed for this report row
Testing period in report2025
UnitpCi/L
Limit or standard fieldMCL Goal: 0; MCL: 5
Status printed for this rowSYSTEM in VIOLATION: NO (row sample period)
Source page2
Source table2025 Annual Treated Drinking Water Quality Report - Inorganic
Report rowBarium (2019)
Reported measurementDetected Level: 8.8
Range in reportNo separate range printed
Sites above action levelNot listed for this report row
Testing period in report2019
UnitPpb
Limit or standard fieldMCL Goal: 2,000; MCL: 2,000
Status printed for this rowSYSTEM in VIOLATION: NO (row sample period)
Source page2
Source table2025 Annual Treated Drinking Water Quality Report - Inorganic
Report rowCopper (2024)
Reported measurementDetected Level: 24
Range in reportNo separate range printed
Sites above action levelNo sites above action level
Testing period in report2024
UnitPpb
Limit or standard fieldMCL Goal: 1300; MCL / AL: 1300 (AL)
Status printed for this rowSYSTEM in VIOLATION: NO (row sample period)
Source page2
Source table2025 Annual Treated Drinking Water Quality Report - Inorganic
Report rowFluoride
Reported measurementDetected Level average: 0.70 avg; 0.70 avg.
Range in report0.5-0.9
Sites above action levelNot listed for this report row
Testing period in reportJanuary 1-December 31, 2025
UnitPpm
Limit or standard fieldMCL Goal: 4; MCL: 4
Status printed for this rowSYSTEM in VIOLATION: NO (row report period)
Source page2
Source table2025 Annual Treated Drinking Water Quality Report - Inorganic
Report rowSelenium (2019)
Reported measurementDetected Level: <MRL
Range in report<MRL
Sites above action levelNot listed for this report row
Testing period in report2019
UnitPpb
Limit or standard fieldMCL Goal: 50; MCL: 50
Status printed for this rowSYSTEM in VIOLATION: NO (row sample period)
Source page2
Source table2025 Annual Treated Drinking Water Quality Report - Inorganic
Report rowLead (2024)
Reported measurementDetected Level: 3.5
Range in reportNo separate range printed
Sites above action levelNo sites above action level
Testing period in report2024
UnitPpb
Limit or standard fieldMCL Goal: 0; MCL / AL: 15 (AL)
Status printed for this rowSYSTEM in VIOLATION: NO (row sample period)
Source page2
Source table2025 Annual Treated Drinking Water Quality Report - Inorganic
Report rowNitrate/Nitrite
Reported measurementDetected Level: 0.033
Range in reportNo separate range printed
Sites above action levelNot listed for this report row
Testing period in reportJanuary 1-December 31, 2025
UnitPpm
Limit or standard fieldMCL Goal: 10; MCL: 10
Status printed for this rowSYSTEM in VIOLATION: NO (row report period)
Source page2
Source table2025 Annual Treated Drinking Water Quality Report - Inorganic

Disinfection byproducts and treatment techniques

Five reported rows, including non-regulatory and treatment-technique results.

Disinfection byproducts and treatment techniques: 2025 annual-report rows for PETERSBURG
Report rowReported measurementRange in reportTesting period in reportUnitLimit or standard fieldStatus printed for this rowSource pageSource table
ChloroformDetected Level maximum: 51.0 max51.0 maxJanuary 1-December 31, 2025PpbMCL Goal: N/A; MCL: Not RegulatedSYSTEM in VIOLATION: NO (row report period)22025 Annual Treated Drinking Water Quality Report - Disinfection By-Products
Total Trihalomethanes (TTHM)Detected Level average: 33.88 avg16.35-51.69January 1-December 31, 2025PpbMCL Goal: N/A; MCL: 80SYSTEM in VIOLATION: NO (row report period)22025 Annual Treated Drinking Water Quality Report - Disinfection By-Products
Total Haloacetic AcidsDetected Level average: 24.59 avg14.80-44.00January 1-December 31, 2025PpbMCL Goal: N/A; MCL: 60SYSTEM in VIOLATION: NO (row report period)22025 Annual Treated Drinking Water Quality Report - Disinfection By-Products
Total Organic CarbonDetected Level average: 76.4% avg60.2--92.3% removalJanuary 1-December 31, 2025TTMCL Goal: 35% to 45% removal (TT); MCL: 35% to 45% removal (TT)SYSTEM in VIOLATION: NO (row report period)22025 Annual Treated Drinking Water Quality Report - Disinfection By-Products
TurbidityDetected Level: 0.27 NTU (Highest); 100% of samples <MCLNo separate range printedJanuary 1-December 31, 2025NTUMCL Goal: N/A; MCL: 95% of samples under 0.3(TT)SYSTEM in VIOLATION: NO (row report period)22025 Annual Treated Drinking Water Quality Report - Disinfection By-Products
Report rowChloroform
Reported measurementDetected Level maximum: 51.0 max
Range in report51.0 max
Testing period in reportJanuary 1-December 31, 2025
UnitPpb
Limit or standard fieldMCL Goal: N/A; MCL: Not Regulated
Status printed for this rowSYSTEM in VIOLATION: NO (row report period)
Source page2
Source table2025 Annual Treated Drinking Water Quality Report - Disinfection By-Products
Report rowTotal Trihalomethanes (TTHM)
Reported measurementDetected Level average: 33.88 avg
Range in report16.35-51.69
Testing period in reportJanuary 1-December 31, 2025
UnitPpb
Limit or standard fieldMCL Goal: N/A; MCL: 80
Status printed for this rowSYSTEM in VIOLATION: NO (row report period)
Source page2
Source table2025 Annual Treated Drinking Water Quality Report - Disinfection By-Products
Report rowTotal Haloacetic Acids
Reported measurementDetected Level average: 24.59 avg
Range in report14.80-44.00
Testing period in reportJanuary 1-December 31, 2025
UnitPpb
Limit or standard fieldMCL Goal: N/A; MCL: 60
Status printed for this rowSYSTEM in VIOLATION: NO (row report period)
Source page2
Source table2025 Annual Treated Drinking Water Quality Report - Disinfection By-Products
Report rowTotal Organic Carbon
Reported measurementDetected Level average: 76.4% avg
Range in report60.2--92.3% removal
Testing period in reportJanuary 1-December 31, 2025
UnitTT
Limit or standard fieldMCL Goal: 35% to 45% removal (TT); MCL: 35% to 45% removal (TT)
Status printed for this rowSYSTEM in VIOLATION: NO (row report period)
Source page2
Source table2025 Annual Treated Drinking Water Quality Report - Disinfection By-Products
Report rowTurbidity
Reported measurementDetected Level: 0.27 NTU (Highest); 100% of samples <MCL
Range in reportNo separate range printed
Testing period in reportJanuary 1-December 31, 2025
UnitNTU
Limit or standard fieldMCL Goal: N/A; MCL: 95% of samples under 0.3(TT)
Status printed for this rowSYSTEM in VIOLATION: NO (row report period)
Source page2
Source table2025 Annual Treated Drinking Water Quality Report - Disinfection By-Products

Disinfectants

One reported chlorine residual row.

Disinfectants: 2025 annual-report rows for PETERSBURG
Report rowReported measurementRange in reportTesting period in reportUnitLimit or standard fieldStatus printed for this rowSource pageSource table
ChlorinePWU average: 0.61 avg.30-.80January 1-December 31, 2025PpmMRDLG: 4.0; MRDL: 4.0SYSTEM in VIOLATION: NO (row report period)2Disinfectants
Report rowChlorine
Reported measurementPWU average: 0.61 avg
Range in report.30-.80
Testing period in reportJanuary 1-December 31, 2025
UnitPpm
Limit or standard fieldMRDLG: 4.0; MRDL: 4.0
Status printed for this rowSYSTEM in VIOLATION: NO (row report period)
Source page2
Source tableDisinfectants
Reported row

Gross Alpha (2025)

Likely source listed in report
Radioactivity caused by Alpha particle emission
Source table
2025 Annual Treated Drinking Water Quality Report - Inorganic

Preservation and source notes

  • The source table's `SYSTEM in VIOLATION` cell is preserved without inferring current compliance or safety status.
Reported row

Radium 226 (2025)

Likely source listed in report
Natural occurring radioactive element
Source table
2025 Annual Treated Drinking Water Quality Report - Inorganic

Preservation and source notes

  • The source table's `SYSTEM in VIOLATION` cell is preserved without inferring current compliance or safety status.
Reported row

Radium 228 (2025)

Likely source listed in report
Natural occurring radioactive element
Source table
2025 Annual Treated Drinking Water Quality Report - Inorganic

Preservation and source notes

  • The source table's `SYSTEM in VIOLATION` cell is preserved without inferring current compliance or safety status.
Reported row

Barium (2019)

Likely source listed in report
Erosion from natural deposits
Source table
2025 Annual Treated Drinking Water Quality Report - Inorganic

Preservation and source notes

  • The source table prints this row with source year 2019; no current-year sampling inference was added.
Reported row

Copper (2024)

Likely source listed in report
Corrosion of household plumbing systems.
Source table
2025 Annual Treated Drinking Water Quality Report - Inorganic

Preservation and source notes

  • The source prints `No sites above action level`; that text is preserved without converting it to a numeric zero or a property-level conclusion.
Reported row

Fluoride

Likely source listed in report
Fluoride is added to the water to promote dental health. Erosion from natural deposits.
Source table
2025 Annual Treated Drinking Water Quality Report - Inorganic

Preservation and source notes

  • The detected-level cell includes both a range and an average; both are preserved without collapsing the row to one unsupported value.
Reported row

Selenium (2019)

Likely source listed in report
Erosion from natural deposits
Source table
2025 Annual Treated Drinking Water Quality Report - Inorganic

Preservation and source notes

  • The report defines MRL as Method Reporting Limit. Less than MRL is not converted to zero or a numeric detection.
Reported row

Lead (2024)

Likely source listed in report
Corrosion of household plumbing systems.
Source table
2025 Annual Treated Drinking Water Quality Report - Inorganic

Preservation and source notes

  • The source prints `No sites above action level`; the annual row cannot determine conditions at a specific property or tap.
Reported row

Nitrate/Nitrite

Likely source listed in report
Surface run off containing vegetation or agricultural pollutants
Source table
2025 Annual Treated Drinking Water Quality Report - Inorganic

Preservation and source notes

  • The combined `Nitrate/Nitrite` source label is preserved without assigning a single-contaminant taxonomy id.
Reported row

Chloroform

Likely source listed in report
Disinfection by-product
Source table
2025 Annual Treated Drinking Water Quality Report - Disinfection By-Products

Preservation and source notes

  • The source prints `Not Regulated` and a `SYSTEM in VIOLATION: NO` cell. Neither is converted into a regulatory finding.
Reported row

Total Trihalomethanes (TTHM)

Likely source listed in report
Disinfection by-products
Source table
2025 Annual Treated Drinking Water Quality Report - Disinfection By-Products

Preservation and source notes

  • The detected-level cell includes both a range and an average; both are preserved without inferring current safety or compliance status.
Reported row

Total Haloacetic Acids

Likely source listed in report
Disinfection by-products
Source table
2025 Annual Treated Drinking Water Quality Report - Disinfection By-Products

Preservation and source notes

  • The source label wraps across two lines; the detected-level range and average are preserved from the same rendered row.
Reported row

Total Organic Carbon

Likely source listed in report
Naturally present in the environment. TOC provides a medium for the formation of disinfection by products.
Source table
2025 Annual Treated Drinking Water Quality Report - Disinfection By-Products

Preservation and source notes

  • The source prints a double hyphen in `60.2--92.3% removal`; it is retained as printed.
Reported row

Turbidity

Likely source listed in report
Soil run off. Turbidity has no health effects but can interfere with disinfection and provide a medium for microbial growth.
Source table
2025 Annual Treated Drinking Water Quality Report - Disinfection By-Products

Preservation and source notes

  • The likely-source field preserves report wording and is not adopted as a current site health conclusion.
Reported row

Chlorine

Likely source listed in report
Water additive to control Microbes
Source table
Disinfectants

Preservation and source notes

  • The disinfectants section uses MRDL/MRDLG columns instead of MCL/MCL Goal columns.

Report Context

Context attributed to the source report

These summaries are limited to the named annual report and do not assert live system, compliance, or advisory status.

Annual-report scope

The Petersburg Water Utility document is a 2025 annual report for PWSID AK2130148. Annual-report statements do not establish live status.

Source-water context

The report identifies Cabin Creek as the primary source and City Creek as a backup source.

Historical source-water assessment

The report references a 2003 source-water assessment. That historical assessment is not a current water-quality finding.

Monitoring scope

The report states a January 1 through December 31, 2025 reporting period while several rows retain older printed sample years.

SOC waiver context

The report describes a Synthetic Organic Chemical monitoring waiver only for the printed 2023 through 2025 cycle.

Lead inventory context

The report says its 2024 inventory identified all lines as Non-Lead. A system-level inventory statement is not property-level proof.

Report-period statistics

Page 2 prints population 3,045 and 1,184 customer connections. These are report-period figures and are not presented as reconciled current profile values.

All reported result rows

This page includes all fifteen rows printed in the report's three result-table sections, including action-level, below-reporting-limit, non-regulatory, and treatment-technique results.

Definitions printed in the report

All eighteen report definitions are transcribed as reading context. They do not create a current compliance or safety conclusion.

Definitions printed in this report

AL
Action Level - The concentration of a contaminant which if exceeded, triggers treatment or other requirements which a water system must follow.
AVG
Average
PWU
Petersburg Water Utility
CDC
Center of Disease Control and Prevention
DEC
Alaska Department of Environmental Conservation
EPA
U.S. Environmental Protection Agency
MCL
Maximum Contaminant Level - The highest level of a contaminant that is allowed in drinking water. MCL's are set as close to the MCLG's as feasible using the best available treatment technology.
MCLG
Maximum Contaminant Level Goal - The level of a contaminant in drinking water below which there is no known or expected risk to health. MCLG's allow for a margin of safety.
MRDL
Maximum Residual Disinfection Level
MRDLG
Maximum Residual Disinfection Level Goal
MRL
Method Reporting Limit
NTU
Nephelometric Turbidity Units
PPM
Parts per million or milligrams per liter
MGD
Million Gallons per Day
PPB
Parts per billion or micrograms per liter
Turbidity
Suspended material or cloudiness
TT
Treatment Technique - A required process intended to reduce the level of a contaminant in drinking water.
pCi/L
Radioactivity Concentration Unit

Report Disclosures

Source-period disclosures kept separate from live status

These items preserve report wording and scope. They do not create violation records, advisory records, or a current-status conclusion.

Source limitation

Annual-report assurance is not a live status finding

Page 1 says the utility's drinking water is safe and meets Federal and State requirements. That wording is retained only as a statement printed in the 2025 annual report; this site does not adopt it as a present-day compliance, safety, advisory, or household-tap conclusion.

Current status is not asserted. Check official current sources for notices or instructions.

Evidence

Official report and system source paths

Use official federal, state, utility, or report sources before treating a page as final.

Report identity and field provenance

  • Official annual report document: Petersburg Borough / Petersburg Water Utility Annual Water Quality Report 2025 Verified two-page PDF with SHA-256 dd280e99341b021e407f85f9986c8d707e187d5ff782ee87ab6b6850577ab8d2.
  • Report, publisher, PWSID, and year: Petersburg Borough / Petersburg Water Utility Annual Water Quality Report 2025 The cover binds Petersburg Water Utility, PWSID AK2130148, and the 2025 reporting year.
  • Current utility report path: Petersburg Borough Water Utility The utility page returned 200 and linked the exact annual report.
  • Current system identity: Alaska DEC Drinking Water Watch for AK2130148 The reviewed state page identifies active community system PETERSBURG using surface water.
  • Dated monitoring-summary context: Alaska DEC monitoring summary for AK2130148 The February 10, 2026 summary lists a corrective action due June 1, 2026; completion is unconfirmed and disclosed on the public report page.
  • Current public-notice archive path: Petersburg Borough Water and Wastewater news archive The filtered archive returned no items, but an archive cannot prove that no current notice exists.

Data and trust

How this report summary is handled

Review the methodology, limitations, and correction process behind the information shown on this page.

Opens in a new tab