Report identity and source
- Public water system
- MOA MUNICIPALITY OF ANCHORAGE
- PWSID
- AK2210906
- Report year
- 2025
- Official publisher/source
- AWWU 2026 Anchorage Drinking Water Quality Report / 2025 Consumer Confidence Report
- Source retrieved
- 2026-07-22
- Last reviewed
- 2026-07-22
Reviewed Report Rows
28 reviewed rows from the 2025 report
Measurements, ranges, units, limit fields, status cells, likely-source wording, and table names remain scoped to the named annual-report rows.
Disinfectants and disinfection by-products
Four reported 2025 rows, including the Total Organic Carbon treatment-technique result.
| Report row | Reported measurement | Range in report | Testing period in report | Unit | Limit or standard field | Status printed for this row | Source page | Source table |
|---|---|---|---|---|---|---|---|---|
| Total Organic Carbon | Highest Detect in Your Water: 12.6; Highest LRAA = 3.15 | ND - 12.6 | 2025 | ppm | MCLG or MRDLG: NA; MCL, TT, or MRDL: TT | Violation / Exceedance: Yes (row sample period) | 5 | Water Quality Monitoring - Regulated Contaminants |
| Chlorine (as Cl2) | Highest Detect in Your Water: 1.5; Distribution System Annual Average = 0.95 | 0.2 - 1.5 | 2025 | ppm | MRDLG: 4; MRDL: 4 | Violation / Exceedance: No (row sample period) | 5 | Water Quality Monitoring - Regulated Contaminants |
| Haloacetic Acids (HAA5) | Highest Detect in Your Water: 7; Highest LRAA = 7 | 1.3 - 7 | 2025 | ppb | MCLG or MRDLG: NA; MCL: 60* | Violation / Exceedance: No (row sample period) | 5 | Water Quality Monitoring - Regulated Contaminants |
| TTHMs [Total Trihalomethanes] | Highest Detect in Your Water: 12.5; Highest LRAA = 12 | ND - 12.5 | 2025 | ppb | MCLG or MRDLG: NA; MCL: 80* | Violation / Exceedance: No (row sample period) | 5 | Water Quality Monitoring - Regulated Contaminants |
Inorganic contaminants
Six reported 2025 rows, including source-water copper and optional sodium without invented primary limits.
| Report row | Reported measurement | Range in report | Testing period in report | Unit | Limit or standard field | Status printed for this row | Source page | Source table |
|---|---|---|---|---|---|---|---|---|
| Barium | Highest Detect in Your Water: 0.0118 | 0.0032 - 0.0118 | 2025 | ppm | MCLG or MRDLG: 2; MCL: 2 | Violation: No (row sample period) | 6 | Inorganic Contaminants |
| Copper - source water | Highest Detect in Your Water: 0.0039 | ND - 0.0039 | 2025 | ppm | MCLG or MRDLG: NA | Violation: No (row sample period) | 6 | Inorganic Contaminants |
| Fluoride | Highest Detect in Your Water: 0.73 | ND - 0.73 | 2025 | ppm | MCLG or MRDLG: 4; MCL: 4 | Violation: No (row sample period) | 6 | Inorganic Contaminants |
| Nitrate [measured as Nitrogen] | Highest Detect in Your Water: 0.873 | ND - 0.873 | 2025 | ppm | MCLG or MRDLG: 10; MCL: 10 | Violation: No (row sample period) | 6 | Inorganic Contaminants |
| Selenium | Highest Detect in Your Water: 11.3 | ND - 11.3 | 2025 | ppb | MCLG or MRDLG: 50; MCL: 50 | Violation: No (row sample period) | 6 | Inorganic Contaminants |
| Sodium (optional) | Highest Detect in Your Water: 7.7 | 4.6 - 7.7 | 2025 | ppm | MCLG or MRDLG: NA | Violation: No (row sample period) | 6 | Inorganic Contaminants |
Microbiological and treatment-technique results
Two reported 2025 rows whose percentages are preserved as treatment or monitoring measures rather than concentrations.
| Report row | Reported measurement | Range in report | Testing period in report | Unit | Limit or standard field | Status printed for this row | Source page | Source table |
|---|---|---|---|---|---|---|---|---|
| Turbidity | Compliance: 100% | Highest single measurement: 0.048 NTU | 2025 | NTU | MCLG or MRDLG: NA; MCL, TT, or MRDL: 0.3 | Violation: No (row sample period) | 6 | Microbiological Contaminants |
| Total Coliform Bacteria | Compliance: All water samples were negative for Total Coliform and E. coli (0% positive) | 0% positive samples | 2025 | per 100 ml | MCLG or MRDLG: 0; MCL: <5% positive | Violation: No (row sample period) | 6 | Microbiological Contaminants |
Lead and copper distribution monitoring
Two reported 2024 action-level rows using 90th-percentile tap-sampling semantics.
| Report row | Reported measurement | Range in report | Sites above action level | Testing period in report | Unit | Limit or standard field | Status printed for this row | Source page | Source table |
|---|---|---|---|---|---|---|---|---|---|
| Copper - action level at consumer taps | Your Water (90th percentile): 0.047* | 0.0028 - 0.309 | 0 | 2024 | ppm | MCLG: 1.3; AL: 1.3 | Exceeds AL: No (row sample period) | 7 | Lead/Copper Distribution Monitoring |
| Lead - action level at consumer taps | Your Water (90th percentile): ND* | ND - 5.14 | 0 | 2024 | ppb | MCLG: 00; AL: 15 | Exceeds AL: No (row sample period) | 7 | Lead/Copper Distribution Monitoring |
Voluntary and secondary monitoring
All fourteen reported page-8 rows remain non-regulatory water-characteristic or secondary-standard context.
| Report row | Reported measurement | Range in report | Testing period in report | Unit | Source page | Source table |
|---|---|---|---|---|---|---|
| Alkalinity (as CaCO3) | Highest Detected Level: 120 | 44 - 120 | 2025 | ppm | 8 | Detected Parameters with Secondary MCLs and Other Parameters of Interest - 2025 |
| Aluminum | Highest Detected Level: 58.3 | ND - 58.3 | 2025 | ppb | 8 | Detected Parameters with Secondary MCLs and Other Parameters of Interest - 2025 |
| Calcium | Highest Detected Level: 37 | 26 - 37 | 2025 | ppm | 8 | Detected Parameters with Secondary MCLs and Other Parameters of Interest - 2025 |
| Chloride | Highest Detected Level: 10.7 | 2.87 - 10.7 | 2025 | ppm | 8 | Detected Parameters with Secondary MCLs and Other Parameters of Interest - 2025 |
| Copper (source water) | Highest Detected Level: 3.94 | ND - 3.94 | 2025 | ppb | 8 | Detected Parameters with Secondary MCLs and Other Parameters of Interest - 2025 |
| Total Hardness (as CaCO3) | Highest Detected Level: 130 | 83 - 130 | 2025 | ppm | 8 | Detected Parameters with Secondary MCLs and Other Parameters of Interest - 2025 |
| Calcium Hardness (as CaCO3) | Highest Detected Level: 93 | 65 - 93 | 2025 | ppm | 8 | Detected Parameters with Secondary MCLs and Other Parameters of Interest - 2025 |
| Magnesium Hardness (as CaCO3) | Highest Detected Level: 41 | 17 - 41 | 2025 | ppm | 8 | Detected Parameters with Secondary MCLs and Other Parameters of Interest - 2025 |
| Magnesium | Highest Detected Level: 10 | 4.1 - 10 | 2025 | ppm | 8 | Detected Parameters with Secondary MCLs and Other Parameters of Interest - 2025 |
| Potassium | Highest Detected Level: 1.3 | 0.32 - 1.3 | 2025 | ppm | 8 | Detected Parameters with Secondary MCLs and Other Parameters of Interest - 2025 |
| Sodium | Highest Detected Level: 7.7 | 4.6 - 7.7 | 2025 | ppm | 8 | Detected Parameters with Secondary MCLs and Other Parameters of Interest - 2025 |
| Sulfate | Highest Detected Level: 45.7 | 8.63 - 45.7 | 2025 | ppm | 8 | Detected Parameters with Secondary MCLs and Other Parameters of Interest - 2025 |
| Total Dissolved Solids | Highest Detected Level: 210 | 130 - 210 | 2025 | ppm | 8 | Detected Parameters with Secondary MCLs and Other Parameters of Interest - 2025 |
| pH | Highest Detected Level: NA | 7.4 - 8.1 | 2025 | SU | 8 | Detected Parameters with Secondary MCLs and Other Parameters of Interest - 2025 |
Total Organic Carbon
- Likely source listed in report
- Naturally present in the environment
- Source table
- Water Quality Monitoring - Regulated Contaminants
Preservation and source notes
- The source attributes the exceedance to the 2025 annual average. July 2025 third-quarter sampling raised the average; October 2025 returned ND, but the average still exceeded the treatment technique. The report says monitoring would increase to monthly in 2026. No current status or resolution is inferred.
Chlorine (as Cl2)
- Likely source listed in report
- Water additive used to control microbes
- Source table
- Water Quality Monitoring - Regulated Contaminants
Preservation and source notes
- The report presents this reported result for the stated sample period. Its printed criteria, value, range, unit, and status remain report-period evidence rather than a current safety, compliance, advisory, resolution, or household-tap conclusion.
Haloacetic Acids (HAA5)
- Likely source listed in report
- By-product of drinking water chlorination
- Source table
- Water Quality Monitoring - Regulated Contaminants
Preservation and source notes
- The report presents this reported result for the stated sample period. Its printed criteria, value, range, unit, and status remain report-period evidence rather than a current safety, compliance, advisory, resolution, or household-tap conclusion.
TTHMs [Total Trihalomethanes]
- Likely source listed in report
- By-product of drinking water disinfection
- Source table
- Water Quality Monitoring - Regulated Contaminants
Preservation and source notes
- The report says THM and HAA monitoring during the 2025 period remained below the printed MCLs. This row does not make a current compliance or safety determination.
Barium
- Likely source listed in report
- Discharge of drilling wastes; Discharge from metal refineries; Erosion of natural deposits
- Source table
- Inorganic Contaminants
Preservation and source notes
- The report presents this reported result for the stated sample period. Its printed criteria, value, range, unit, and status remain report-period evidence rather than a current safety, compliance, advisory, resolution, or household-tap conclusion.
Copper - source water
- Likely source listed in report
- Corrosion of household plumbing systems; Erosion of natural deposits
- Source table
- Inorganic Contaminants
Preservation and source notes
- The source prints 0.0039 only as the highest detected result. It is not an MCL. A distinct voluntary table row prints the same measurement as 3.94 ppb with a secondary standard of 1000 ppb.
Fluoride
- Likely source listed in report
- Erosion of natural deposits; Water additive which promotes strong teeth; Discharge from fertilizer and aluminum factories
- Source table
- Inorganic Contaminants
Preservation and source notes
- The report presents this reported result for the stated sample period. Its printed criteria, value, range, unit, and status remain report-period evidence rather than a current safety, compliance, advisory, resolution, or household-tap conclusion.
Nitrate [measured as Nitrogen]
- Likely source listed in report
- Runoff from fertilizer use; Leaching from septic tanks, sewage; Erosion of natural deposits
- Source table
- Inorganic Contaminants
Preservation and source notes
- The report presents this reported result for the stated sample period. Its printed criteria, value, range, unit, and status remain report-period evidence rather than a current safety, compliance, advisory, resolution, or household-tap conclusion.
Selenium
- Likely source listed in report
- Discharge from petroleum and metal refineries; Erosion of natural deposits; Discharge from mines
- Source table
- Inorganic Contaminants
Preservation and source notes
- The report presents this reported result for the stated sample period. Its printed criteria, value, range, unit, and status remain report-period evidence rather than a current safety, compliance, advisory, resolution, or household-tap conclusion.
Sodium (optional)
- Likely source listed in report
- Erosion of natural deposits; Leaching
- Source table
- Inorganic Contaminants
Preservation and source notes
- The report presents this reported result for the stated sample period. Its printed criteria, value, range, unit, and status remain report-period evidence rather than a current safety, compliance, advisory, resolution, or household-tap conclusion.
Turbidity
- Likely source listed in report
- Soil runoff
- Source table
- Microbiological Contaminants
Preservation and source notes
- The 100% value is a treatment-performance percentage, not a contaminant concentration.
Total Coliform Bacteria
- Likely source listed in report
- Naturally present in the environment
- Source table
- Microbiological Contaminants
Preservation and source notes
- The report presents this reported result for the stated sample period. Its printed criteria, value, range, unit, and status remain report-period evidence rather than a current safety, compliance, advisory, resolution, or household-tap conclusion.
Copper - action level at consumer taps
- Likely source listed in report
- Corrosion of household plumbing systems; Erosion of natural deposits
- Source table
- Lead/Copper Distribution Monitoring
Preservation and source notes
- The source describes 2024 tap sampling after at least six hours of standing time. The result is system-level 90th-percentile evidence, not a measurement for every tap.
Lead - action level at consumer taps
- Likely source listed in report
- Corrosion of household plumbing systems; Erosion of natural deposits
- Source table
- Lead/Copper Distribution Monitoring
Preservation and source notes
- The source prints the MCLG cell as 00 and the 90th-percentile value as ND*. Both are preserved without normalization. This is system-level 2024 tap-sampling evidence, not a result for every household tap.
Alkalinity (as CaCO3)
- Likely source listed in report
- Erosion of carbonate deposits; dissolved CO2
- Source table
- Detected Parameters with Secondary MCLs and Other Parameters of Interest - 2025
Preservation and source notes
- The report presents this reported row in its voluntary monitoring and secondary-standards table. It is report-period, non-regulatory context rather than a primary health-limit or current-condition finding.
Aluminum
- Likely source listed in report
- Erosion of natural deposits; residue from some surface water treatment processes
- Source table
- Detected Parameters with Secondary MCLs and Other Parameters of Interest - 2025
Preservation and source notes
- The report presents this reported row in its voluntary monitoring and secondary-standards table. It is report-period, non-regulatory context rather than a primary health-limit or current-condition finding.
Calcium
- Likely source listed in report
- Erosion of natural deposits
- Source table
- Detected Parameters with Secondary MCLs and Other Parameters of Interest - 2025
Preservation and source notes
- The report presents this reported row in its voluntary monitoring and secondary-standards table. It is report-period, non-regulatory context rather than a primary health-limit or current-condition finding.
Chloride
- Likely source listed in report
- Erosion of natural deposits; seawater influence
- Source table
- Detected Parameters with Secondary MCLs and Other Parameters of Interest - 2025
Preservation and source notes
- The report presents this reported row in its voluntary monitoring and secondary-standards table. It is report-period, non-regulatory context rather than a primary health-limit or current-condition finding.
Copper (source water)
- Likely source listed in report
- Erosion of natural deposits
- Source table
- Detected Parameters with Secondary MCLs and Other Parameters of Interest - 2025
Preservation and source notes
- This is the voluntary page-8 row with a secondary standard. It is distinct from the page-6 source-water Copper row printed as 0.0039 ppm with no MCL.
Total Hardness (as CaCO3)
- Likely source listed in report
- Dissolved calcium and magnesium
- Source table
- Detected Parameters with Secondary MCLs and Other Parameters of Interest - 2025
Preservation and source notes
- The report presents this reported row in its voluntary monitoring and secondary-standards table. It is report-period, non-regulatory context rather than a primary health-limit or current-condition finding.
Calcium Hardness (as CaCO3)
- Likely source listed in report
- Dissolved calcium
- Source table
- Detected Parameters with Secondary MCLs and Other Parameters of Interest - 2025
Preservation and source notes
- The report presents this reported row in its voluntary monitoring and secondary-standards table. It is report-period, non-regulatory context rather than a primary health-limit or current-condition finding.
Magnesium Hardness (as CaCO3)
- Likely source listed in report
- Dissolved magnesium
- Source table
- Detected Parameters with Secondary MCLs and Other Parameters of Interest - 2025
Preservation and source notes
- The report presents this reported row in its voluntary monitoring and secondary-standards table. It is report-period, non-regulatory context rather than a primary health-limit or current-condition finding.
Magnesium
- Likely source listed in report
- Dissolved limestone or minerals
- Source table
- Detected Parameters with Secondary MCLs and Other Parameters of Interest - 2025
Preservation and source notes
- The report presents this reported row in its voluntary monitoring and secondary-standards table. It is report-period, non-regulatory context rather than a primary health-limit or current-condition finding.
Potassium
- Likely source listed in report
- Erosion of natural deposits
- Source table
- Detected Parameters with Secondary MCLs and Other Parameters of Interest - 2025
Preservation and source notes
- The report presents this reported row in its voluntary monitoring and secondary-standards table. It is report-period, non-regulatory context rather than a primary health-limit or current-condition finding.
Sodium
- Likely source listed in report
- Erosion of natural deposits; fertilizers, animal waste, landfills or other waste
- Source table
- Detected Parameters with Secondary MCLs and Other Parameters of Interest - 2025
Preservation and source notes
- The report presents this reported row in its voluntary monitoring and secondary-standards table. It is report-period, non-regulatory context rather than a primary health-limit or current-condition finding.
Sulfate
- Likely source listed in report
- Erosion of natural deposits; mine drainage waste
- Source table
- Detected Parameters with Secondary MCLs and Other Parameters of Interest - 2025
Preservation and source notes
- The report presents this reported row in its voluntary monitoring and secondary-standards table. It is report-period, non-regulatory context rather than a primary health-limit or current-condition finding.
Total Dissolved Solids
- Likely source listed in report
- Erosion of natural deposits
- Source table
- Detected Parameters with Secondary MCLs and Other Parameters of Interest - 2025
Preservation and source notes
- The report presents this reported row in its voluntary monitoring and secondary-standards table. It is report-period, non-regulatory context rather than a primary health-limit or current-condition finding.
pH
- Likely source listed in report
- Not listed for this report row
- Source table
- Detected Parameters with Secondary MCLs and Other Parameters of Interest - 2025
Preservation and source notes
- The report presents this reported row in its voluntary monitoring and secondary-standards table. It is report-period, non-regulatory context rather than a primary health-limit or current-condition finding.
Report Context
Context attributed to the source report
These summaries are limited to the named annual report and do not assert live system, compliance, or advisory status.
Annual-report scope
The official document is the MOA MUNICIPALITY OF ANCHORAGE 2025 Consumer Confidence Report, published by AWWU for PWSID AK2210906 in 2026. Its statements and measurements are annual-report evidence, not live status.
Source-water context
The report identifies Eklutna Lake and Ship Creek surface water plus groundwater from six active Anchorage Bowl wells. This is report-period source context rather than a live operating inventory.
Source-water assessment
The report reproduces Alaska DEC susceptibility and vulnerability classifications for named surface-water and well sources. Those assessment categories are not household-tap measurements or current safety findings.
Treatment context
The report describes filtration and disinfection as the system's treatment processes. This summary does not infer a current operating condition or compliance result.
Lead and service-line context
The report describes an ongoing service-line inventory, says no known lead service lines were identified, notes unknown compositions remain, and identifies 2024 lead and copper tap sampling.
Lead and copper sampling context
The report describes 2024 tap sampling on a three-year cycle after at least six hours of standing time. The 90th-percentile rows remain system-level evidence rather than household-tap results.
Complete modeled result scope
This page preserves all 28 printed result rows: fourteen regulated, treatment-technique, action-level, or other rows and fourteen voluntary or secondary rows. The source notes that some required monitoring data may be more than one year old.
Source-water non-detect list
The report lists named inorganic analytes and 23 volatile organic compounds as monitored but not detected in source waters in 2024. They are retained as narrative context rather than invented result rows.
Report-period Total Organic Carbon follow-up
The report says Total Organic Carbon sampling at the source would increase from quarterly to monthly in 2026 to monitor conditions and determine whether additional treatment was needed. Completion or current resolution is not asserted.
Voluntary and secondary table scope
All fourteen page-8 rows are rendered as non-regulatory water-characteristic or secondary-standard evidence with their source units and ranges intact.
Definitions printed in the report
All six unit descriptions on page 8 and all twelve drinking-water definitions on page 9 are transcribed for reading context. They do not create a current compliance or safety conclusion.
Definitions printed in this report
- ppm
- ppm: parts per million, or milligrams per liter (mg/L)
- ppb
- ppb: parts per billion, or micrograms per liter (µg/L)
- NTU
- NTU: Nephelometric Turbidity Units. Turbidity is a measure of the cloudiness of the water. We monitor it because it is a good indicator of the effectiveness of our filtration system.
- NA
- NA: not applicable
- ND
- ND: Not detected
- NR
- NR: Monitoring not required, but recommended.
- Contaminant
- Contaminant: Any physical, chemical, biological, or radiological substance or matter in water.
- MCLG
- MCLG: Maximum Contaminant Level Goal: The level of a contaminant in drinking water below which there is no known or expected risk to health. MCLGs allow for a margin of safety.
- MCL
- MCL: Maximum Contaminant Level: The highest level of a contaminant that is allowed in drinking water. MCLs are set as close to the MCLGs as feasible using the best available treatment technology.
- TT
- TT: Treatment Technique: A required process intended to reduce the level of a contaminant in drinking water.
- AL
- AL: Action Level: The concentration of a contaminant which, if exceeded, triggers treatment or other requirements which a water system must follow.
- Variances and Exemptions
- Variances and Exemptions: State or EPA permission not to meet an MCL or a treatment technique under certain conditions.
- LRAA
- LRAA: Locational Running Annual Average: The average of analytical results for samples taken at a particular monitoring location in the four most recent calendar quarters.
- MRDLG
- MRDLG: Maximum residual disinfection level goal. The level of a drinking water disinfectant below which there is no known or expected risk to health. MRDLGs do not reflect the benefits of the use of disinfectants to control microbial contaminants.
- MRDL
- MRDL: Maximum residual disinfectant level. The highest level of a disinfectant allowed in drinking water. There is convincing evidence that addition of a disinfectant is necessary for control of microbial contaminants.
- MNR
- MNR: Monitored Not Regulated
- MPL
- MPL: State Assigned Maximum Permissible Level
- 90th Percentile
- Compliance with the lead and copper action levels is based on the 90th percentile lead and copper levels. This means the concentration of lead and copper must be less than or equal to the action level in at least 90% of the samples collected.
How to read a water quality report
A plain-English walkthrough of Consumer Confidence Reports, including report years, detected contaminants, legal limits, violations, and source notes.
View How to read a water quality reportReport Disclosures
Source-period disclosures kept separate from live status
These items preserve report wording and scope. They do not create violation records, advisory records, or a current-status conclusion.
Annual report is not current status
The document reports on 2025 and was published in 2026. Its result cells and narrative do not establish current compliance, advisory status, resolution, or conditions at a household tap.
Current status is not asserted. Check official current sources for notices or instructions.
Annual-report assurance is not a live status finding
The official report says AWWU complied with drinking-water regulations and met state and federal standards in 2025. This site attributes that statement to the report period and does not adopt a present-day safety, compliance, advisory, or household-tap conclusion.
Current status is not asserted. Check official current sources for notices or instructions.
Service-line inventory is not property-level proof
The report says no known lead service lines were identified in the MOA system while lines of unknown composition remained. That system-level report statement does not establish the material at a specific property.
Current status is not asserted. Check official current sources for notices or instructions.
System sampling is not a household-tap result
The report's 2024 lead and copper rows are system-level 90th-percentile evidence from selected taps. They do not describe every household tap, service line, or plumbing configuration.
Current status is not asserted. Check official current sources for notices or instructions.
2025 Total Organic Carbon treatment-technique exceedance
The report attributes the exceedance to the 2025 annual average, says July sampling raised that average, says October returned ND while the average still exceeded the treatment technique, and says monthly monitoring would begin in 2026. This is not a claim about current violation, notice, resolution, compliance, or safety status.
Current status is not asserted. Check official current sources for notices or instructions.
Secondary standards are not primary health limits
The report describes the page-8 values as voluntary monitoring and non-mandatory secondary standards used for aesthetic considerations such as taste, color, or odor. This page does not convert them into primary health-based limits.
Current status is not asserted. Check official current sources for notices or instructions.
Evidence
Official report and system source paths
Use official federal, state, utility, or report sources before treating a page as final.
Utility website
Utility website
Utility website
Utility website
Utility report
Report identity and field provenance
- Official annual report document: AWWU 2026 Anchorage Drinking Water Quality Report / 2025 Consumer Confidence Report Verified nine-page PDF with SHA-256 8b9277cbd19766eb2301864f8cc96f298b4ce4f68bc5ee3417ad32cfefdea9ee.
- Report, publisher, PWSID, and year: AWWU 2026 Anchorage Drinking Water Quality Report / 2025 Consumer Confidence Report The document binds MOA MUNICIPALITY OF ANCHORAGE, PWSID AK2210906, the 2025 report period, and AWWU publisher context.
- Current public-water-system identity: Alaska DEC identity record for AK2210906 The state record supports the official PWS name and identifier; AWWU remains operator and publisher context.
- State monitoring-summary context: Alaska DEC monitoring summary for AK2210906 Verified five-page summary with SHA-256 a848621b753952721fb9f82b62096ebf9dee629d236fe8fec13c57912910ee1e; it is used for identity and classification context, not a live notice conclusion.
- Official annual-report archive: AWWU drinking water quality reports The AWWU archive separates the Anchorage and Girdwood reports; Girdwood is excluded from this report contract.
- Official current-information paths: AWWU outages, emergency, water-quality concern, and news paths The linked official paths are places to check current information. Their reviewed state cannot prove that no current notice exists or that current conditions match the annual report.
MOA MUNICIPALITY OF ANCHORAGE profile
Return to the evergreen public water-system profile and its broader source context.
View MOA MUNICIPALITY OF ANCHORAGE profileAnchorage city page
Return to the city-to-system browse path without treating city boundaries as the water service area.
View Anchorage city pageData and trust
How this report summary is handled
Review the methodology, limitations, and correction process behind the information shown on this page.
Methodology
Review source hierarchy, PWSID matching, and missing-data handling.
View MethodologyLimitations
See why annual report summaries are not live status or complete laboratory history.
View LimitationsCorrections
Send an official source if a report identity, row, or link needs review.
View Corrections